Introduction
Features
Installation
Install where required by code, where doors may be used to confine smoke or fire, or wherever remote control or automatic closing doors are required. • Be sure door hardware and trim projections are compatible with total projection of door release. • Anchor the electromagnet firmly since the wall portion will function as a door stop. • Locate magnet approximately 6 inches in from lock edge of door. Wall magnets should be mounted approximately 2 to 4 feet above the floor for optimum performance. • Door-mounted contact plate includes hardware for through-bolting or concealed mounting. • Spotting template included with unit ensures correct alignment. • 14AWG. Max. Wire Size.
Product Description & Features
• Total Projection: 7/16"(11mm) • Mounting Requirements: 2" x 4" x 2-1/2"(51 x 102 x 64mm) outlet box • Wall must be properly reinforced and outlet box adequately fastened • UL listed door holder
Technical Information • Voltage and Current: 120 VAC, 60 Hz., .020 amp 24 VAC/DC, 60 Hz., .020 amp 12 VDC, .040 amp 250 VAC, 50/60 Hz., .009 amp
Finishes
• 689 Sprayed Aluminum (SA) • 690 Sprayed Dark Bronze (SB) • 691 Sprayed Light Bronze (SLB) • 696 Sprayed Gold (SG)