Q: Are we able to order just the armature extensions?
A: You sure can. What length do you need?
Q: I would need 2 sets. 16 inches long with 2 sets of swivels each.
A: The 16" extension is here:
Click Here
and should contain everything needed.
Q: Can I use my Radionics D7024 fire alarm panel as seen here:
View Image
to control the dropping out or the opening of the circuit for the ABH 2100 Electromagnetic Recessed Wall Mount Door Holder?
A: Most certainly you can. The manual for the Radionics D7024 can be viewed here:
Download File
You will want to review the section 2.2.4 Relays and be sure through the software to reset the relay so that it operates the way in which you require it to do so.
You would set the relay to utilize the common and normally open portion of the relay in this will allow you to power your electromagnetic door holders which will keep the doors open at all times until there is a fire alarm condition present on the panel which will then set the relay to its natural state which because you're using normally open would cut the power through the relay allowing your doors to the energized and therefore closed via the normal mechanical hardware installed on the doors..
For further questions I would recommend that you contact the manufacturer directly and their phone number can be found on the very bottom of the very last page of the manual.
Q: What wires can we use if 120Volts AC will be the supply voltage of the electromagnetic door holder?
A: Run your not and neutral to the common and 120v terminals as seen in the installation instructions here:
Download File
Q: i am curious if i can order a 1 inch extension and the ball that attaches to the magnet. also if i could get instructions on how to do so.
A: Yes you can order the ABH 20100 US2G 1" Magnetic Release Armature Extension - Zinc Plated and instructions are provided with the piece:
Click Here